SBS Pipe Frost Protection Panel

nVent RAYCHEM SBS-FP-xx-16 A control panel provides an integrated solution for nVent RAYCHEM self-regulating heating cables in pipe freeze protection applications. It offers multi-circuits, each with line sensing control or proportional ambient sensing control (PASC) with integrated electrical protection. A 400 VAC (3 phase) supply is required.

Specification Details

Please note that these product properties are not a replacement for the manufacturer's literature and it is always recommended that nVent Solutions (UK) Limited - Raychem Trace Heating / TraceTek Leak Detection is consulted before specifying.

nVent Solutions (UK) Limited - Raychem Trace Heating / TraceTek Leak Detection
3 Rurtherford Road
Washington
United Kingdom
NE37 3HX
P: 07730503452

SBS Pipe Frost Protection Panel

Elexant 450c / Elexant 450c-Modbus
• Exposure Temperature: 0 - 40 C
• Features: Alarm relay with change over contact to signal power or temperature or communication problems, Controls 2 independent heating circuits, DIN rail panel mountable, Flexible temperature control of pipe freeze protection and temperature maintenance systems, Intuitive set-up and programming of the unit, Offsite configurable, Pipe line sensing and/or ambient sensing, Pipe line temperature monitoring with high and low temperature alarm, Proportional Ambient Sensing Control (PASC) algorithm for enhanced energy savings in ambient sensing mode, The Elexant 450c-Modbus is equipped with a RS485 port for Modbus communication to a BMS system
• IP Rating: IP 20
• Voltage AC: 230 VAC
• CE Marking: Yes
• Typical Use: Non-hazardous locations
• Material: PPE
• Mounting Type: DIN-Rail mountable 35 mm
• Product Type: Electronic Controller for Pipe Freeze Protection and Temperature Maintenance Systems
• Storage Temperature: -20 - 50 °C
• Depth: 56 mm
• Height: 110 mm
• Width: 158 mm

SBS-FP-3x16A
• Circuit breaker: 3 x 25A
• Exposure Temperature: 10 - 35 C
• Features: Circuit over-current and RCD protection integrated directly into the control panel, Collective error / alarm, Complete system directly from the manufacturer, Connection of 3–12 heating circuits to a single control panel, Fast connection of multiple heating circuits directly to the control panel, No additional connections or junction boxes required, No separate safety devices required, The system and components have been selected for optimal use as a pipe freeze protection and temperature maintenance systems
• IP Rating: IP 65
• Max. Quantity of Heating Circuits: 3
• Max.Quantity of Controller Elexant 450c: 1
• Sensor Type: NTC-Type
• CE Marking: Yes
• Product ID Number: SBS-FP-3x16A
• Depth: 210 mm
• Height: 600 mm
• Weight: 20 kg
• Width: 400 mm
• Colour: Grey
• Material: Sheet steel wall-mounted enclosure
• Mounting Type: Wall-mounted
• Product Type: Panels for pipe freeze protection and temperature maintenance

SBS-FP-6x16A
• Circuit breaker: 3 x 32A
• Exposure Temperature: 10 - 35 C
• Features: Circuit over-current and RCD protection integrated directly into the control panel, Collective error / alarm, Complete system directly from the manufacturer, Connection of 3–12 heating circuits to a single control panel, Fast connection of multiple heating circuits directly to the control panel, No additional connections or junction boxes required, No separate safety devices required, The system and components have been selected for optimal use as a pipe freeze protection and temperature maintenance systems
• IP Rating: IP 65
• Max. Quantity of Heating Circuits: 6
• Max.Quantity of Controller Elexant 450c: 1
• Sensor Type: NTC-Type
• CE Marking: Yes
• Product ID Number: SBS-FP-6x16A
• Depth: 210 mm
• Height: 600 mm
• Weight: 32 kg
• Width: 600 mm
• Colour: Grey
• Material: Sheet steel wall-mounted enclosure
• Mounting Type: Wall-mounted
• Product Type: Panels for pipe freeze protection and temperature maintenance

SBS-FP-9x16A
• Circuit breaker: 3 x 63A
• Exposure Temperature: 10 - 35 C
• Features: Circuit over-current and RCD protection integrated directly into the control panel, Collective error / alarm, Complete system directly from the manufacturer, Connection of 3–12 heating circuits to a single control panel, Fast connection of multiple heating circuits directly to the control panel, No additional connections or junction boxes required, No separate safety devices required, The system and components have been selected for optimal use as a pipe freeze protection and temperature maintenance systems
• IP Rating: IP 65
• Max. Quantity of Heating Circuits: 9
• Max.Quantity of Controller Elexant 450c: 2
• Sensor Type: NTC-Type
• CE Marking: Yes
• Product ID Number: SBS-FP-9x16A
• Depth: 210 mm
• Height: 800 mm
• Weight: 54 kg
• Width: 800 mm
• Colour: Grey
• Material: Sheet steel wall-mounted enclosure
• Mounting Type: Wall-mounted
• Product Type: Panels for pipe freeze protection and temperature maintenance

SBS-FP-12x16A
• Circuit breaker: 3 x 80A
• Exposure Temperature: 10 - 35 C
• Features: Circuit over-current and RCD protection integrated directly into the control panel, Collective error / alarm, Complete system directly from the manufacturer, Connection of 3–12 heating circuits to a single control panel, Fast connection of multiple heating circuits directly to the control panel, No additional connections or junction boxes required, No separate safety devices required, The system and components have been selected for optimal use as a pipe freeze protection and temperature maintenance systems
• IP Rating: IP 65
• Max. Quantity of Heating Circuits: 12
• Max.Quantity of Controller Elexant 450c: 2
• Sensor Type: NTC-Type
• CE Marking: Yes
• Product ID Number: SBS-FP-12x16A
• Depth: 210 mm
• Height: 800 mm
• Weight: 56 kg
• Width: 800 mm
• Colour: Grey
• Material: Sheet steel wall-mounted enclosure
• Mounting Type: Wall-mounted
• Product Type: Panels for pipe freeze protection and temperature maintenance